MCN Engineered Systems: Large Networks with Routers and 1.25 Mbps Backbones

MCN and BRSC Monitoring · Last updated · About 3 min read

How MCN systems scale beyond 20 comparator I/O modules with routers, a 1.25 Mbps backbone and factory-set addresses.

A standard MCN network segment is limited to 20 comparator I/O modules, 1200 feet and a single 78 kbps network (mcn-installation-addressing-cabling-and-power). Larger systems are engineered systems: CTI engineers design a custom network, document it with system drawings and module configuration spreadsheets, and support it during and after installation.

What defines an engineered system

An MCN system is an engineered system when it has more than 20 comparator I/O modules and/or when it has a router. A router limits the flow of specified data to part of a network and joins networks of different bus speeds. Routers raise overall network performance by attaching to a high-speed 1.25 Mbps network and reducing the amount of data that flows into a slower 78 kbps area. In the manual's example, three routers join a 1.25 Mbps backbone to several 78 kbps segments, each with up to 20 CIB modules, with a PC using a dual-channel PCLTA card and an HIB with a dial-up modem line as user interfaces. Routers are installed in an original router manifold or in the newer Quad Router Panel, a rack assembly that holds up to four routers (blank plates cover unused positions) and is electrically compatible with the older routers.

Two network types

The manual distinguishes a TP/FT-10 (78 kbps) network and a TP/XF-1250 (1.25 Mbps) network. Terminators are required at both ends of both kinds and are specific to each type: a 1.25 Mbps terminator must never be connected to a 78 kbps network. For the 1.25 Mbps network they are generally fitted on the first and last 1.25 Mbps RJ-45 connectors of the router manifold, or, when a PCLTA card is the last connection, a terminator on a wire (which must not be lengthened).

Identification and addresses

  • Every module has a model label on its rear panel giving its acronym, part number (the last three digits are the revision) and serial number. Many MCN products look alike, so verify the unit type before installation. Open boards such as PCLTA cards and test boards carry their label on the board; routers and EXB modules also carry a label saying how they are programmed.
  • Modules with address switches have their Group and Module numbers set at the factory for an engineered system, and the manual says not to change any engineered-system unit address. Two modules with the same address cause improper and possibly unintended operation.
  • Modules without switches (PCLTA cards, EXB modules and routers) are configured by software. PCLTA addresses are set in the configuration program; routers and EXBs are preconfigured with scripts that use unique addresses defined by CTI so they do not conflict with other addresses in the network.

Why this matters

Engineered systems are how MCN scaled to wide-area voting networks and master/sub comparator systems with comparators at many sites joined by EXB extenders over leased lines, microwave or IP. Later IP-based software (mcn-server-8000-and-ip-modules) reaches similar sizes with standard IP networking.