Installing an MCN System: Addressing, Cabling, Mounting and Power

MCN and BRSC Monitoring · Last updated · About 5 min read

How MCN modules are addressed with Group and Module numbers, receiver banks, network cabling limits, terminators, mounting and DC power chaining.

This article summarizes the installation chapters of the MCN system manual and planner. The system itself is described in mcn-monitoring-and-control-network-overview. Every module ships with default switch settings, so each must be configured for its application before it goes into service; the module's own hardware reference manual describes its switches.

Installation steps

  1. Determine the addresses of all MCN modules.
  2. Set the Group and Module numbers on each module.
  3. Set each module's option switches, and the receiver bank number on IIB modules. HIB addresses are entered into the PC when the display software is installed.
  4. Mount the modules.
  5. Route the network cables, connect the modules, and put a terminator at each end of the network.
  6. Connect power supplies.
  7. Connect each comparator I/O module to its comparator, and each user-interface module to its operator station.
  8. Check each module's manual for additional setup.
  9. Power up: on every module the PWR LED should be on, ACT on or blinking and ERR off (an HIB's ACT LED blinks only when the display software is running and a screen configuration is loaded).
  10. Test, and use mcn-troubleshooting-and-module-indicators if something is wrong.

Unit addresses

Each module is identified by a unique address made of a Group number (00 to FE) and a Module number (0 to F), set with rotary switches (the HIB's are entered in the PC software). Group FF is reserved: a module set to it halts with its ERR LED on. Changing a Group or Module number requires a reset or power cycle. All modules in a system must have unique addresses; duplicates cause improper operation and possibly unintended control. The IIB and TIB need two addresses: their own, and that of the module they work with.

Address planning guidelines

  • Put comparator I/O modules in one Group (or set of Groups if there are more than 16 modules), starting at Group 00, Module 0, leaving room for expansion.
  • Put user-interface modules in their own Group or Groups starting at Group 80, Module 0.
  • If several MCN systems may later be joined with EXB modules, use unique addresses across all of them from the start.
  • A PC running the display software through an HIB can watch only four Groups at a time, so plan addresses so that the receivers watched together fall in as few Groups as possible.
  • Keep a worksheet of unit type, Group, Module, bank, the module each IIB or TIB works with, and notes. The manual shows an example with comparator rooms A and B using Groups 01 and 02, a dispatch room using Group 80 and a maintenance site using Group 81.

Receiver banks

A comparator I/O module that supports more than 8 receivers divides them into banks of 8: bank 0 is receivers 1 to 8, bank 1 is 9 to 16, and so on up to bank 7 (57 to 64). HIBs with the display software support only bank 0. An IIB can be configured for any one bank. In the manual's example an ASTRO-TAC comparator with 13 receivers is split into banks 0 and 1, with one IIB set to each. CIBs and HIBs are factory-set to bank 0; AIBs to banks 0 and 1.

Network cabling

Item Specification
Cable 4-pair Level IV or V unshielded twisted pair, 24 AWG (EIA/TIA 568B), straight-through. Ordinary telephone cable will not work. 2-pair cable (data pair only) can be used
Modules per segment Maximum 20
Segment length Maximum 1200 feet
Topology Daisy chain from NETWORK OUT to NETWORK IN; a terminator (100-ohm resistor) in the unused port of the first and last modules
Cables from CTI Standard lengths up to 100 feet, joined with couplers; their use is recommended

The RJ-45 network connectors are not Ethernet ports. The later HIB-IP 8002 manual warns that they may carry DC power and that connecting them to an Ethernet device can damage it.

Power

  • Input is 10 to 32 VDC, most modules needing no more than 2 W. CTI's plug-in supplies provide 18 VDC at 800 mA; the system's noise and impulse immunity was tested only with them, and other supplies may reduce performance or void emissions approvals. The DC IN jack accepts either plug polarity.
  • Power chaining: the network cable carries power as well as data, so one supply can power several modules. At most four modules per supply, and at most 100 feet of cable between modules sharing a supply. An EXB counts as two modules. Connect the supply to the first module and chain NETWORK OUT to NETWORK IN; add another supply at any module when the limits are exceeded (the example needs two supplies for four modules because one link is longer than 100 feet).
  • For runs over 100 feet with your own cable, a new supply is needed at the far end.
  • For critical sites the DC distribution panel supplies two hot-standby supplies.

Mounting and grounding

  • Wall mount: a bracket on the module's bottom (two screw holes on A-size modules, four on B-size). Use only the flat-head screws supplied, or ones that protrude no more than 1/8 inch into the case, to avoid touching the circuit board.
  • Rack mount: a 19-inch bracket holds four modules (four A-size, or two A-size and one B-size). The module's front panel and bezel are removed and refastened to the bracket. Do not let the circuit board slide out of the case; if it does, it must be reinserted from the rear. Nothing inside is user serviceable.
  • Digitac bracket: only the CIB has a special bracket for mounting on the back of a Digitac comparator, needing an additional 2.181 inches of clearance behind it.
  • Grounding: every module has a chassis ground screw hole on the bottom, with the same 1/8-inch limit on screw length.

Source documents

This article summarizes the following published CTI Products manuals. They are the authoritative reference.

This article is part of the CTI Products Knowledge Base. Questions about RadioPro or MCN products? Call +1 (513) 595-5900 or email info@ctiproducts.com.